INPUT
Input voltage (~3 Phase) 230-500V (-20% to +10%)
(~3 Phase) 690V (-20% to +10%)
Supply frequency 47 to 62 Hz
Control voltage 230V ±10%, others under demand
   
OUTPUT
Output voltage 0 to 100% supply voltage
Output frequency Same as the input
Efficiency (at full load) > 99%
   
ENVIRONMENTAL CONDITIONS
Ambient temperature Minimum: -10°C / Maximum: +50°C
Storage Temperature 0°C to +70°C
Ambient Humidity < 95%, non-condensing
Altitude losses >1000m, 1% each 100m; 3000m max
Protection degree IP20
Degree of Pollution Degree of Pollution 3
   
MOTOR PROTECTIONS
Input phase missing
High current
Low input voltage
Starting limit current
Rotor locked
Motor overload (thermal model)
Underload
Phase imbalance
Motor overtemperature (PTC, normal status 150R-2k7Ω)
Shearpin current
Number of start /hour
   
SOFTSTARTER PROTECTIONS
Thyristor fault
V5 over temperature
   
ADJUSTMENTS
Torque surge
Initial torque
Initial torque time
Acceleration time
Current limit: 1 to 5 In
Overload: 0.8 to 1.2 In, Overload slope: 0 to 10
Deceleration time / Freewheel stop
DC braking
Slow Speed (1/7 fundamental frequency)
Dual setting
Number of starts allowed
Torque control
Water hammer surge control stop
For additional information consult the technical manual
   
INPUT SIGNALS
2 analogue inputs, 0-20mA or 4-20mA, 0-10V
5 configurable digital inputs
1 PTC input
   
OUTPUT SIGNALS
1 output signal 0-20mA or 4-20mA
3 changeover output relays (250VAC, 10A non inductive)
   
SERIAL COMMUNICATIONS
Phisical level RS232/RS485
Modbus communication industrial protocol
Profibus and DeviceNet via interface (options)
   
DISPLAYED INFORMATION
Phase current
Supply voltage
Relays status
Digital inputs / PTC status
Analogue inputs value
Analogue output value
Overload status
Motor supply frequency
Motor power factor
Developed power, motor shaft torque
Fault history (5 most recent faults)
   
SOURCES CONTROL
Local via keypad
Remote via digital inputs
Remote via Serial Communications (MODBUS, RS232/RS485)
   
LED'S INDICATIONS
LED 1 Green, voltage present on control board
LED 2 Orange, Blinking, Motor accelerating / decelerating
             On, motor running
LED 3 Red, fault present
   

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

© Power Electronics 2010